PM04x
- SMS/GPRS/CAMERA/RF/WIFI Remote Monitoring Terminal

Specification: PM040 - 16 Digital Input (Dry Contact, DC to 30V)
PM041 - 8 Digital Input, 4 ADC 0 - 5V (16bit), 1 Latch Relay Output (2A)
Power Supply: DC 7V to 20VDC.
LCD Display: BackLite 20 Character x 2 Line LCD
LCD Display GSM Network Signal Strength, System Date/Time, Status.
PC Interface: RS232C for Setup and Console Interactive Status Display,
Event Logging
Optional: Build in Digital Camera for still picture capture and
send to server
Optional:: RS232C (or Rs485) to interface to external datalogger
Battery Backed Real Time Calender Clock provide event date/time stamping.
Multiple Event Notification: Concatenated SMS message to reduce the
number of SMS send out.
Optional: RF Modem Interface, WiFi Interface instead of GSM Modem
Optional: Ethernet LAN for TCPIP Interface.
Antenna: External High Gain Antenna.
Operate on either Standalone, Server Base or Combine Standalone + Server
Base.
APPLICATION AREA
Remote Event Alarm Notification. (UPS, Cold Room, Refrigeration,
Electrical, Breaker, Solar Panel, Security Panel, Fire Alarm Panel, Lift
Monitoring).
Remote System Reset via Wireless Means. The Relay output
contact can be used to remotely reset your system or activate your remote
system external trigger.
Operation Mode
PM04x support dual operating mode:
a) Direct SMS Message Send to User Handphone.
When Alarm Event occurs, Message are compose and then send
directly to user handphone. The number of failed Send SMS can be set to
automatically retry sending after a user specified interval.
b) Server Mode: Send to Testech SMSMONV2 HMI Sotware
When Alarm Event occurs, Message are compose and compressed and
then send to Testech HMI Software running at the customer central monitoring PC
equipped with a SMS/GPRS Modem. Using GPRS has the added advantage that the
Remote Monitor can be an online systems (that is continous update on the PC).
Note that GPRS typicaly requires user to have subscription service to Telco
unlike of the shelve PrePaid SIM Card.
This means that with our RTU you are assure of the best in both world of
operating in standalone mode, Server Mode, and BOTH SIMULTANEOUS User+Server
Mode by creating different Phone/IP group on the PM04x..
The important implication is that our RTU is scalable, allowing customer to
gradually scaled up the unit of deployment from standalone base to server base.
GROUP CONFIGURATION AND ASSIGNMENT
Up to 6 Group of 5 Phone Each (that is total of 30 GSM Phone Number) can be
setup on the RTU (via RS232C or Keypad)
Group can be set to Server Mode (requires SMSMONV2 HMI Software) or User
Mode (diret SMS Message Alert to user Mobile Phone)
Group can be Enable or Disable.
Inputs assignment can be asigned to each Group. For example if the
RTU are connected to mechanical equipments, HVAC and electrical equipment
etc and there are different team of maintenance responsible for each
category of equipments, you can then alert ONLY the team that are
responsible for the particular input that requires service attention when a
alarm is send out via SMS
Each group and each individual phone can be individually enable and
disable. Inputs can be assigned to different group.
PHONE CONFIGURATION AND ASSIGNMENT
Total of 30 GSM Phone number can be created in the PM04x RTU, by
assigning up to 5 Phone Max to Each group (max 6 Groups).
Each Phone can be assign two different privilege mode
Supervisor Phone: Supervisor Phone can configure the unit and send
control command to the unit (Turn Alarm ON/OFF, switch RTU to Online GPRS
Mode, Switch RTU to OffLine SMS Mode, Turn Relay On, Snap Pictre,
Change Phone Number, Enable/Disable Phone, Enable/DIsable Group)
User Phone: User Phone are only allow to receive alarm message via SMS or
Poll the System (for example to check the input status again, or health
check).
DIGITAL INPUT CONFIGURATION AND ASSIGNMENT
Each Input can be individually setup to trigger SMS on Low, High, Alarm
Limit Low or Alarm Limit High.
System Status can be check by sending a SMS message (?SQ) to check RTU
Health Status.
System can be ARM, DisARM for maintenance.
ANALOG INPUT CONFIGURATION AND ASSIGNMENT (PM041)
Each Analog Input resolutions is 16bit instrumentation grade Aanalog To
Dgiital Converter accepts unipolar (0-5V). 4-20mA can be measure by
connecting a 1% 250ohm resistor to convert the input to 1-5V.
Each Channel can be individually configure for zero and span,
engineering scaling.
Engineering Scaling: The Low Reading and Full Scale Reading can be scaled
to user Engieering Units up to 4 digitals + 1 decimal Place (-9.999 to
+999.9)
Low Alarm and Hysterisis: Low Alarm can be set with hysterisis (that is
if input falls below the Low Alarm trip point), SMS wll be send and the
Alarm will only be clear if input reovers to Low Alarm trip point +
hysterisis.
High Alarm and Hysterisis: High Alarm can be set with hysterisis (that is
if input rises above the High Alarm trip point), SMS wll be send and the
Alarm will only be clear if input reovers to Low Alarm trip point +
hysterisis.
ANALOG ADC CALIBRATION
The ADC can be calibrated by the user by using a voltage calibrator. Each
ADC has 5 points digital calibration for the best linearity. During
calibration, the value read in are compare against against accept value.
PM041 uses FULL Digital calibration and there is no TrimPot or
Potentiometer. Thefore the long term stability of ADC reading is very good.
RELAY OUTPUT
PM041 has 1 Relay Output able to handle up to 2A current. This relay can
be user for example interface to external Light Pole, Siren, Reset External
Equipment etc.
CAMERA
PM040 or PM041 canbe optionally factory installed with a digital camera
onboard to allows user to snap picture (preview picture or Max VGAx640 pixel
resolution). Picture taken can be send via GRPS back to SMSMONV2 HMI
Software
PC Interface (RS232)
Console interface using any Serial Terminal Software such as Windows
HyperTerminal for interactive login, system setup,
maintenance check, and configure of Input Description, Alarm Trigger, Group,
Phone Number.
Changes made can be save into PM04x interval Non Volatile Memory to
permanently store the setup.

EVENT LOGGING
All Event (System Login, System Reset, IO Event, Send SMS Operations etc)
are logged and save in battery backup memory. Up to 100 event are invidually
time stamed and store in the event log.
RS232C/RS485
The PM04x has a optional External RS232C to allow interface to external
peripheral and equipment such as datalogger, please talk to us for any
custom interfacing including RS232C/RS485. For example we can interface to
GPS/Datalogger/Swipe Card Reader etc.
ETHERNET LAN
In Proccess of implementation, FULL TCPIP stack with Ethernet LAN 10BT,
for Wired LAN remote Monitoring application and built in HTTP WebServer.
|