INTRODUCTION The
WEA01 is a low cost wireless GSM/GPRS Real Time SCADA Systems for Weather
Station Monitoring that is design to be deployed in remote areas for RainFall
Level Monitoring, User selectable rain gauge tip level can be easily program to
match the tipping bucket (0.1mm, 0.2mm, 0.5mm etc) LCD Display And Keypad Entry Large 20 char x 2 line BackLit LCD shows system status, date and time as well as all status of outgoing and incoming SMS, GPRS packet, and provide system diagnostic information and calibration. Keypad allows unit to be setup and calibrate locally without PC in the field SENSOR
CALIBRATION AND ALERT LIMIT, ENABLE Event DATE/TIME STAMP All Event are date and time stamps to record the actual time of alarm. RealTime Clock/Calender are backup via Lithium Battery lasting > 5years. Low cost SMS Logger For RainFall a simple low cost SMS Logger is provided to log rainGauge and export the data to Excel Format for user analysis of Rain Fall or the RainFall graph and data can be view on the PC at request.
CONTINOUS UPDATE VIA GPRS For Realtime continuously monitoring (as short as 5sec interval), the data are stream to the SCADA HMI that requires a Broadband Internet connection. Built in Quad Band GSM/GPRS The PM051E Wireless Telemetry Datalogger as controller which has a built in CE/FCC Approved Quad Band Industrial Class Robust GSM/GPRS Module. High Precision Analog IOs, Digital IOs, Relay Ouputs The PM051E has 8 protected digital input, 2 protected Fast Edge Detect Input (Active Low), and 4 High Precision 16 bit ADC High speed sampling of 1MHZ, 4-20mA, with a usable more than 30,000 count resolution input in the 4-20mA measurement Range. The 3 LATCH relay output are resettable fuse protected for up to 2.5A at 24V and is suitable to drive SIREN, Beacon Lights or to activate external controls. Analog Input uses digital calibration (up to 5 points) allows very precision digital calibration (no adjustment required). 4-20mA input has a input impedanace of only 10ohm and can be connected in series with existing user instrumentation such as thru a chart recorder and will not add to the exiting loop impedance. These Analog Input can be use for water and wastewater/sewer qualities measurement, continious waterLevel Measurement, and datalog and send SMS alert or upload data wirelesslessly via GPRS. The relay output is possible to turn on external Pump for example. or contact us for any custom interfacing as the PM051E has built in TCPIP, UDP, USB, RS232C, RS485 interfaces. Datalogger Memories Built in 4MB Datalogger Memories, and external insertable MicroSD Card support 1GB of FAT file systems allows usr to datalog IO at a user set interval. Built in Http Webserver
Built in HMI Webserver allows user to view IO status, Web Setup. Tough Enclosure Tough Metal WeatherProof Enclosure with Waterproof and cable gland, robust cabling. Dimension 400 mm H x 300 mm W x 200mm D Power Requirement 12V @ 0.12A (1.2W norminal Power), Solar Panel and Battery 12V SLA
|
|
Back to M2M Main Page | Back to Testech Home Page | Water/Weather Instrumentations |